Configuring a GCNET Fire Network
Scenario
You want to configure Desigo CC for connecting fire control panels (Desigo Fire Safety Modular and Cerberus Pro Modular only) on a GCNET network.
For related information, see:
- VNT Configuration in GCNET
- Block Commands and System Behavior
- Ownership of XNET Fire Panels
- UL/ULC Compliance: XNET Fire Panel Settings section in the Compliance Notice for UL Norms page or Compliance Notice for ULC Norms page.
Prerequisites
- The extension modules corresponding to the specific fire panels in use were installed and included in the active project. They can be either of the following:
- Desigo Fire Safety Modular UL
- Cerberus Pro Modular UL - In the Zeus tool, you have configured all the XNET networks (buildings) of the GCNET.
In Zeus, from Tools > CreateVNT (GCNET) Configuration, select the XNET networks (buildings) and click Create to create the gms_gcnet.xml file in the GCNET subfolder of the Zeus path.
NOTE: Subsequently, to update the exiting configuration, select the modified buildings only.
Overview