Desigo Fire Safety Modular System Limits and Compatibility

For system limits relating to the network configuration, search for XNET in Compliance Notice for UL Norms or Compliance Notice for ULC Norms.

For compatibility information, see the following table.

Compatible Versions and Firmware

Panel

Version

Firmware

Modular

V14.01.xxxx (MP1.05)
V14.02.xxxx (MP1.1)
V14.03.xxxx (MP1.2)
V14.04.xxxx (MP1.3)
V14.05.xxxx (MP1.4)
V15.00.xxxx (MP2.0)
V15.00.xxxx (MP3.0)

Zeus D V14.01.xxxx
Zeus D V14.02.xxxx
Zeus D V14.03.xxxx
Zeus D V14.04.xxxx
Zeus D V14.05.xxxx
Zeus D V15.00.xxxx
Zeus D V15.01.xxxx

Only single XNET networks with a maximum of 16 panels are supported.

NOTE 1: Firmware 15 (V2.0) and Zeus V15 are required for compliance with ULC S527 4th edition.

NOTE 2: In the FS20M Zeus configuration (up to V15.00.xxxx), if the NFPA System Type is configured as Proprietary, the Self Restoring Troubles and Self Restoring Supervision options in the Behavior must not be selected.

Fire WAN Compatibility