Treating FS20 Fire and Carbon Monoxide (CO) Detection Troubles

Trouble treatment can include multiple steps. The following procedure presents a typical scenario. You can suspend/resume this procedure at any step.

  1. (Optional) Select the event (one at the time).
    NOTE: The next expected command (Acknowledge, Silence, or Reset) is directly available for each event in Event List without any selection.
  2. Click Acknowledge .
  3. This informs the local panels that the event treatment is started on the management station.
  4. Depending on the specific situation, start the required counter-measures to address the actual trouble situation in the equipment.
  5. Ensure that the trouble condition has terminated.
  6. Click Reset to reset the alarm.
  7. Click the event button.
  1. The event is cleared from Event List.