Treating FS20 Fire and Carbon Monoxide (CO) Detection Troubles
Trouble treatment can include multiple steps. The following procedure presents a typical scenario. You can suspend/resume this procedure at any step.
- (Optional) Select the event (one at the time).
NOTE: The next expected command (Acknowledge, Silence, or Reset) is directly available for each event in Event List without any selection. - Click Acknowledge
.
- This informs the local panels that the event treatment is started on the management station.
- Depending on the specific situation, start the required counter-measures to address the actual trouble situation in the equipment.
- Ensure that the trouble condition has terminated.
- Click Reset
to reset the alarm.
- Click the event button.
- The event is cleared from Event List.