Message Optimization Parameters

This expander is available only for Reno Plus license users.

Provides a way to group the events raised in quick succession and triggers a consolidated message (summary incident) describing the event burst situation.
NOTE: Message optimization is applicable only to the New state of the events.

  • Enable: Allows you to enable or disable message optimization parameters for an incident template.
  • Burst time: Allows you to configure time window (in seconds) which will be considered when alarm shower occurs. Burst time can be incremented in multiple of 30s.
  • Burst threshold: Allows you to configure number of incidents that can be triggered per burst time window in case of alarm shower.
  • Burst text: Allows you to configure text content to be delivered in summary incident which is triggered due to alarm shower. Burst text will replace text content along with variables configured in message template.