(Optional) Configure room representation for RDF302 room thermostat

(Optional) Configure room representation for RDF302 room thermostat

The graphical representation of the room can be configured according to the installed components. Information on the graphical display is available RDF302 Room Variants in the Graphic.

  1. Select Project > Field networks > [RDF302 Network] > [Interfacename] > [RDF302 room thermostat].
  1. In the Advanced operation tab, select property Engineering FNC position.
    a. Select Change.
    b. From the Value drop-down list box , select Roof or Window.
    c. Select Send.
  1. In the Advanced operation tab, select property Plant type configuration.
    a. Select Change.
    b.. From the Value drop-down list box, select one of the following options:
    - None
    - 2-pipe system
    - 2-pipe, 3-position
    - 2-pipe with electric heating
    - 4-pipe system
    c. Select Send.
  • The selected setting is applied and the graphic is updated.