Compatibility List

The following network, hardware, firmware, Integration Drivers, and FLN applications are compatible for integration with Desigo CC.

APOGEE Networks Supported

Network

Supported

Additional Requirements

P2 RS-485

Y

RS-485 networks can be connected using AEM; however, direct connection is not supported.

P2 AEM

Y

Requires one of the following:

Physical AEM device

Virtual AEM in a PXC

P2 Ethernet

Y

Supported as is.

P2 Dial-Up

X

Not supported. Must be converted to Ethernet network or AEM.

BACnet IP

Y

Supported as is.

ALS3

X

Not supported.

 

Hardware Supported

Hardware

Type

ALN

MBC Power Open Processor (562-001,002,040)

MBC Open Processor

MEC Power Controller (549-600 series)

MEC Controller

PXC Compact

PXC Modular

Hardware

Type

FLN P1

P1DXR

TEC

LAB Controllers

Point Expansion Modules

PXC Compact on P1

P1 BIM

Digital Energy Monitor

P1 Drivers

VFD

Hardware

Type

FLN BACnet

DXR (APOGEE Firmware Revision 3.4 and later)

PTEC

PXC UEC

PPM

 

Firmware Supported

The following list shows hardware and drivers compatible with minimal GMSnode:1891511861649583471004  firmware support.

It is recommended that you install\flash to the latest firmware available to ensure the best system performance and to install the most recent bug fixes.

FLNC

Hardware

2.x P2 RS-485

2.x P2 Ethernet

3.x BACnet

FLNC

2.8

2.7

N/A

PXC

Hardware

2.x P2 RS-485

2.x P2 Ethernet

3.x BACnet

PXC

2.8.20

2.8.20

3.5.5

PXC Drivers

2.8.2 or 2.8.5

(See Driver Availability List)

2.8.2 or 2.8.5

(See Driver Availability List)

3.1 Ver. 2

(See Driver Availability List)

MBC

Hardware

2.x P2 RS-485

2.x P2 Ethernet

3.x BACnet

Power Open Processor

2.8.20

2.8.20

Limited Support*

Power Open Processor Drivers

2.7

2.7

Limited Support*

Pre Power OP

2.8.20

N/A

N/A

Pre Power OP Drivers

Not Supported

N/A

N/A

*Will look like a third–party BACnet device.

MEC

Hardware

2.x P2 RS-485

2.x P2 Ethernet

3.x BACnet

Power MEC (V3)

2.8.20

2.8.20

Limited Support*

Power MEC (V3) Drivers

2.7

2.7

Limited Support*

Pre Power MEC (68302)

2.8.20

N/A

N/A

Pre Power MEC Drivers

Not Supported

N/A

N/A

SCU

Hardware

2.8 P2 RS-485

2.8 P2 Ethernet

3.x BACnet

SCU v5

Not Supported

N/A

N/A

 

FLN Drivers Supported

The following list shows Integration Drivers compatible with BACnet firmware (APOGEE Firmware Revision 3.2.4 and later):

Driver Name

Current APOGEE Firmware Revision

BACnet MS/TP

3.2

Barber Colman Network 8000 Enhanced Driver

3.1

CSI Host

3.1

Johnson Controls N2 Master

3.2

Konnex

3.1

Modbus

3.2

Modbus 250

3.2

Pneumercator

3.1

Siemens Firefinder XLS

3.2

Siemens SiPass

3.2

Trane

3.1

Veeder Root

3.1

Veeder Root Enterprise

3.1

YORK ISN Enhanced

3.1

 

FLN Application Support

Applications listed in the FLN Application Library are fully supported with pre-defined Functions and Template Graphics. While applications not found in the list are discovered and imported, you must manually create and assign Functions and Template Graphics. In this case, contact Technical Support for help.