FS20 Fire Network Operating Troubleshooting
This section contains troubleshooting information for FS20 Desigo Fire control panels.
Handle Event Problems in Operating Mode
Problem | Situation | Do the following... |
Cannot silence events from Desigo CC stations. In the Event List, the silence command icon is missing. | The silence inhibit has been configured on the panel and is currently active. The silence command is only allowed after a predefined delay. |
|
All control commands have no effects. | Network connection is down: all object properties show #COM state and object symbols in graphics display a yellow grid. |
|
Cannot erase the Client UI Missing event. | The Client UI Supervision trouble does not automatically disappear due to incompatibility between Desigo CC and FS20 panels with firmware 3.0 and 3.1 |
|