PDLDAT
PPCL command that defines the minimum on-time, minimum off-time, maximum off-time, and kilowatt value for a specific load. A group of PDLDAT commands are used in conjunction with a single PDL command in a "load handling" field panel to define load parameters and maintain a certain kilowatt level (or target) for that group of loads.