Start a BACnet Driver

  • System Manager is in Engineering mode.
  • You have already added a BACnet driver, and you need to finish configuring and starting it.
  1. In System Browser, select Management View.
  1. Depending on where the BACnet Driver is located (Desigo CC server or FEP station), do one of the following:
  • Select Project > Management System > Servers > Main Server > Drivers
  • Select Project > Management System > FEPs > [FEP station] > Drivers
  1. Click the BACnet tab (which finishes configuring the BACnet driver).
  1. Click the Extended Operation tab.
  1. In the Manager Status property, click Start.
  • The BACnet driver is now ready to use.